44 ControlLogix
Analog HART Modules
Input Input
Input Input
Input
TT
TT
T
aa
aa
a
gsgs
gsgs
gs
The following fault and status reporting and module data sections allow
monitoring of faults, status, and input data from the module. These tags
can be found within the If8h0Input controller tag.
Table 5.3a
Tag Name Data Type Style Description
If8h0Input If8h0InputBlock NA Module input data
If8h0Input.ModuleStatus DINT BIN General module status
If8h0Input.ModuleStatus.0 BOOL DEC Channel 0 general fault status
0 = No fault
1 = Fault
If8h0Input.ModuleStatus.1 BOOL DEC Channel 1 general fault status
0 = No fault
1 = Fault
If8h0Input.ModuleStatus.2 BOOL DEC Channel 2 general fault status
0 = No fault
1 = Fault
If8h0Input.ModuleStatus.3 BOOL DEC Channel 3 general fault status
0 = No fault
1 = Fault
If8h0Input.ModuleStatus.4 BOOL DEC Channel 4 general fault status
0 = No fault
1 = Fault
If8h0Input.ModuleStatus.5 BOOL DEC Channel 5 general fault status
0 = No fault
1 = Fault
If8h0Input.ModuleStatus.6 BOOL DEC Channel 6 general fault status
0 = No fault
1 = Fault
If8h0Input.ModuleStatus.7 BOOL DEC Channel 7 general fault status
0 = No fault
1 = Fault
If8h0Input.ModuleStatus.8 BOOL DEC Channel 0 broken wire
0 = Connection
1 = Open circuit
If8h0Input.ModuleStatus.9 BOOL DEC Channel 1 broken wire
0 = Connection
1 = Open circuit
If8h0Input.ModuleStatus.10 BOOL DEC Channel 2 broken wire
0 = Connection
1 = Open circuit
If8h0Input.ModuleStatus.11 BOOL DEC Channel 3 broken wire
0 = Connection
1 = Open circuit
If8h0Input.ModuleStatus.12 BOOL DEC Channel 4 broken wire
0 = Connection
1 = Open circuit