Chapter 2: Installation and Wiring 2-7
User'sManualPub.030024302Rev.B
!
Attention
EXPLOSION HAZARD
In Class I, Division 2 applications, the bus connector must be
fully seated and the bus connector cover must be snapped in
place.
In Class I, Division 2 applications, all modules must be
mounted in direct contact with each other as shown on page 2-
5. If DIN rail mounting is used, an end stop must be installed
ahead of the controller and after the last 1762 I/O module.
Section 2.6
Field Wiring
Connections
Consider the following when wiring your system:
General
Power and input wiring must be in accordance with Class 1, Division 2 wiring
methods, Article 501-4(b) of the National Electric Code, NFPA 70, and in
accordance with the authority having jurisdiction.
Channels are isolated from one another by ±10 Vdc maximum.
If multiple power supplies are used with analog millivolt inputs, the power
supply commons must be connected.
Terminal Block
Do not tamper with or remove the CJC sensor on the terminal block. Removal of
the sensor reduces accuracy.
For millivolt sensors, use Belden 8761 shielded, twisted-pair wire (or
equivalent) to ensure proper operation and high immunity to electrical noise.
For a thermocouple, use the shielded, twisted-pair thermocouple extension lead
wires specified by the thermocouple manufacturer. Using the incorrect type of
thermocouple extension wire or not following the correct polarity will cause
invalid readings.
To ensure optimum accuracy, limit overall cable impedance by keeping a cable
as short as possible. Locate the module as close to input devices as the
application permits.
Grounding
!
Attention
The possibility exists that a grounded or exposed thermocouple can
become shorted to a potential greater than that of the thermocouple
itself. Due to possible shock hazard, take care when wiring grounded or
exposed thermocouples.
!
Attention
USE SUPPLY WIRES SUITALE FOR 20°C ABOVE SURROUNDING
AMBIENT