1-2 MicroLogix™ 1200 IO Universal Input Module
User'sManualPub.030024302Rev.B
Input Type Range
N Type Thermocouple -210 to 1300 ˚C (-346 to 2372 ˚F)
R Type Thermocouple 0 to 1768 ˚C (32 to 3214 ˚F)
S Type Thermocouple 0 to 1768 ˚C (32 to 3214 ˚F)
T Type Thermocouple -270 to 400 ˚C (-270 to 752 ˚F)
100 Pt α 0.385 -200 to 850 ˚C (-328 to 1562 ˚F)
200 Pt α 0.385 -200 to 850 ˚C (-328 to 1562 ˚F)
500 Pt α 0.385 -200 to 850 ˚C (-328 to 1562 ˚F)
1000 Pt α 0.385 -200 to 850 ˚C (-328 to 1562 ˚F)
100 Pt α 0.3916 -200 to 630 ˚C (-328 to 1166 ˚F)
200 Pt α 0.3916 -200 to 630 ˚C (-328 to 1166 ˚F)
500 Pt α 0.3916 -200 to 630 ˚C (-328 to 1166 ˚F)
1000 Pt α 0.3916 -200 to 630 ˚C (-328 to 1166 ˚F)
10 Cu α 0.426 -100 to 260 ˚C (-148 to 500 ˚F)
100 Ni α 0.618 -100 to 260 ˚C (-148 to 500 ˚F)
120 Ni α 0.672 -80 to 260 ˚C (-112 to 500 ˚F)
604 NiFe α 0.518 -100 to 200 ˚C (-148 to 392 ˚F)
Resistance
0 to 150
0 to 1000
0 to 3000
Voltage
+/- 50 mV
+/- 100 mV
0 to 5V
1 to 5V
+/- 10V
0 to 10V
Current
4 to 20 mA
0 to 20 mA
Section 1.3
Data Formats
For each module the data can be configured for:
Engineering units x 1
Engineering units x 10
Scaled-for-PID
Raw/proportional data
Section 1.4
Filter
Frequencies
The module uses a digital filter that provides high frequency noise rejection for each
input signal. The filter for each channel is programmable allowing you to select from four
different filter frequencies:
4 Hz
17 Hz
62 Hz
470 Hz