Spectrum-controls 1762sc-IF8U User Manual Page 21

  • Download
  • Add to my manuals
  • Print
  • Page
    / 38
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 20
User'sManualPub.030024302Rev.B
Chapter 3
Configuring the 1762sc-IF8u
Using RSLogix 500
This chapter covers the following subjects:
Things you should know
Module memory map
Add module to Logix 500
Module configuration
Reading input data
Module update time
Section 3.1
Things You
Should Know
This chapter describes how to configure the IF8u module for the MicroLogix 1100, 1200
and 1400 system using RSLogix 500 programming software.
Section 3.2
Module Memory
Map
The module uses 8 input words and 8 output words for input data and configuration. The
following figure describes the data mapping for the module.
Input Image
I:0 to I:7( 8 words)
(Input Data)
Output Image
O:0 to O:7 (8 words)
(Configuration Data)
1762sc-IF8u
Read
Write
Figure 3-1 (Module Memory Map)